Environmental Monitoring

Dubbo Sewage Treatment Plant

The Dubbo Sewage Treatment Plant is licenced by the NSW Environment Protection Authority. The licence number is 3850.

Dubbo Sewage Treatment Plant Environment Protection Licence Dubbo Sewage Treatment Plant Environment Protection Licence (139 KB)

For more information about licences, click here: http://www.environment.nsw.gov.au/epa/.

Effluent leaving the Dubbo Sewage Treatment Plant is monitored in accordance with the terms of the licence. Licencees are required to publish pollution monitoring data that has been collected as a result of a licence condition, in accordance with section 66(6) of the POEO Act and written requirements issued by the EPA.

 

The Dubbo Sewage Treatment Plant has two discharge points. The tables below refer to to Point 1, which is the point of discharge to the Macquarie River. The monitoring frequency for this point is weekly, when it is necessary to discharge effluent to the River. 

 

 

Monthly Result for April 2013 - No Macquarie River discharges from Sampling Point 1 during April

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet.   

Monthly Result for March 2013 - No Macquarie River discharges from Sampling Point 1 during March

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet.   

Monthly Result for February 2013 - No Macquarie River discharges from Sampling Point 1 during February

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet. 

Monthly Result for January 2013 - No Macquarie River discharges from Sampling Point 1 during January

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet. 

Monthly Result for December 2012 - No Macquarie River discharges from Sampling Point 1 during December

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet. 

Monthly Result for November 2012 - No Macquarie River discharges from Sampling Point 1 during November

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet. 

Monthly Result for October 2012 - No Macquarie River discharges from Sampling Point 1 during October

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet. 

Monthly Result for September 2012 - No Macquarie River discharges from Sampling Point 1 during September

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical  Oxygen Demand

0-30

mg/L

1

Chlorophyll a

N/A

mg/L

1

Conductivity

N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet.  

Monthly Result for August 2012 - Effluent discharged to Macquarie River

Sampling Point

Pollutant

Acceptable Range

Unit

Result:

7/08

Result:

14/08

Result: 21/08

Result:

28/08

Av.

Min. 

Max. 

1

Biochemical  Oxygen Demand

0-30

mg/L

 11  3  5  6 6.25

3

11

1

Chlorophyll a

N/A

mg/L

 2.3 0.6  0.4  0.8 1.025

0.4

2.3

1

Conductivity

N/A

µS/cm

 980.6  1037  862.5  876.1 939.05

862.5

1037

1

Faecal Coliforms

0-200

cfu/100mL

 0   0  30 290 80

0

290

1

Nitrogen (total)

0-15

mg/L

 3.25  2.26  2.57  5.2 3.32

2.26

5.2

1

Oil and Grease

0-10

mg/L

 2.5  2.5  2.5 2.5 2.5

2.5

2.5

1

Phosphorus (total)

0-10

mg/L

 8.24 8.76  4.45  5.9 6.8375

4.45

8.76

1

Total Suspended Solids

0-30

mg/L

 13 4 1 7 6.25

1

13

1

pH

6.5-8.5

pH

7.4 7.8 7.8  7.4 7.6

7.4

7.8

Right click on the table above to export as a spreadsheet.

Monthly Result for July 2012 - Effluent discharged to Macquarie River

Sampling Point

Pollutant

Acceptable Range

Unit

Result: 03/07

Result: 10/07

Result: 19/07

Result: 24/07

Result:

31/07

Av.

Min. 

Max. 

1

Biochemical  Oxygen Demand

0-30

mg/L

1

 4  4  3  2 2.8

1

4

1

Chlorophyll a

N/A

mg/L

 0.1

 4.2  0.9  0.9  0.5 1.32

0.1

4.2

1

Conductivity

N/A

µS/cm

 1161

 906  990.7  999.4  998.6 1011.1

906

1161

1

Faecal Coliforms

0-200

cfu/100mL

 0

 0  920  0  0 306.67

0

920

1

Nitrogen (total)

0-15

mg/L

 6.3

 5.2  4.22  4.9  5.5 5.24

4.22

6.3

1

Oil and Grease

0-10

mg/L

 1.5

 1.5  2.5  1.5  2.5 1.83

1.5

2.5

1

Phosphorus (total)

0-10

mg/L

 3.46

 5.88 1.29  5.5  5.68 3.54

1.29

5.88

1

Total Suspended Solids

0-30

mg/L

 7

 6  7  4  6 6.67

6

7

1

pH

6.5-8.5

pH

 7.8

 7.7  7.6  7.6  7.5 7.7

7.6

7.8

Right click on the table above to export as a spreadsheet

 

Monthly Result for June 2012 - Effluent discharged to Macquarie River

Sampling Point

Pollutant

Acceptable Range

Unit

Result: 05/06

Result: 12/06

Result: 18/06

Result: 26/06

Av.

Min. 

Max. 

1

Biochemical  Oxygen Demand

0-30

mg/L

1

 1  4  4

2.5

1

4

1

Chlorophyll a

N/A

mg/L

4

 1.1  7.3  1.8

3.55

1.1

7.3

1

Conductivity

N/A

µS/cm

1005

 920.9  923.6  921

942.625

920.9

1005

1

Faecal Coliforms

0-200

cfu/100mL

2200

 2000  880  5300

2595

880

5300

1

Nitrogen (total)

0-15

mg/L

9.1

 7.2  8.6  8.75

8.4125

7.2

9.1

1

Oil and Grease

0-10

mg/L

1.5

 1.5  1.5  1.5

1.5

1.5

1.5

1

Phosphorus (total)

0-10

mg/L

5.25

 3.38  5.05  4.62

4.575

3.38

5.25

1

Total Suspended Solids

0-30

mg/L

4

 2  7  15

7

2

15

1

pH

6.5-8.5

pH

7.8

 7.6  7.5  7.6

7.625

7.5

7.8

Right click on the table above to export as a spreadsheet.

Monthly Result for May 2012 - Effluent discharged to Macquarie River

Sampling Point

Pollutant

Acceptable Range

Unit

Result: 30/05/2012

Average

Min. 

Max. 

1

Biochemical Oxygen Demand

0-30

mg/L

1

1

1

1

1

Chlorophyll a

N/A

mg/L

0.2

0.2

0.2

0.2

1

Conductivity

N/A

µS/cm

998

998

998

998

1

Faecal Coliforms

0-200

cfu/100mL

0.5

0.5

0.5

0.5

1

Nitrogen (total)

0-15

mg/L

5

5

5

5

1

Oil and Grease

0-10

mg/L

1.5

1.5

1.5

1.5

1

Phosphorus (total)

0-10

mg/L

3.25

3.25

3.25

3.25

1

Total Suspended Solids

0-30

mg/L

4

4

4

4

1

pH

6.5-8.5

pH

7.5

7.5

7.5

7.5

Right click on the table above to export as a spreadsheet.

Monthly Result for April 2012 - No Macquarie River discharges from Sampling Point 1 during April

Sampling Point

Pollutant

Acceptable Range

Unit

1

Biochemical Oxygen Demand

0-30

mg/L

1

Chlorophyll a

 N/A

mg/L

1

Conductivity

 N/A

µS/cm

1

Faecal Coliforms

0-200

cfu/100mL

1

Nitrogen (total)

0-15

mg/L

1

Oil and Grease

0-10

mg/L

1

Phosphorus (total)

0-10

mg/L

1

Total Suspended Solids

0-30

mg/L

1

pH

6.5-8.5

pH

Right click on the table above to export as a spreadsheet.

 

Point 2 refers to monthly discharge of effluent to effluent irrigation. The licence does not state acceptable ranges for pollutants at this Point. Note that fewer pollutants are required to be monitored at Point 2, as compared to Point 1.

 

 

Date Sample Taken:3/04/2013

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

5

mg/L

2

Nitrogen (total)

5.6

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

6.18

mg/L

2

Total Suspended Solids

1

mg/L

Right click on the table above to export as a spreadsheet. 

Date Sample Taken:6/03/2013

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

10

mg/L

2

Nitrogen (total)

8

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

6.15

mg/L

2

Total Suspended Solids

9

mg/L

Right click on the table above to export as a spreadsheet.   

Date Sample Taken:6/02/2013

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

17

mg/L

2

Nitrogen (total)

22.8

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

8.16

mg/L

2

Total Suspended Solids

29

mg/L

Right click on the table above to export as a spreadsheet.  

Date Sample Taken:8/1/2013

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

40

mg/L

2

Nitrogen (total)

14.2

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

7.72

mg/L

2

Total Suspended Solids

41

mg/L

Right click on the table above to export as a spreadsheet. 

Date Sample Taken:4/12/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

10

mg/L

2

Nitrogen (total)

3.9

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

5

mg/L

2

Total Suspended Solids

13

mg/L

Right click on the table above to export as a spreadsheet.

Date Sample Taken:6/11/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

8

mg/L

2

Nitrogen (total)

3.01

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

5.8

mg/L

2

Total Suspended Solids

7

mg/L

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 3/10/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

5

mg/L

2

Nitrogen (total)

3.05

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

6.06

mg/L

2

Total Suspended Solids

4

mg/L

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 4/09/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

 3

mg/L

2

Nitrogen (total)

2.4

mg/L

2

Oil and Grease

1.5

mg/L

2

Phosphorus

5.22

mg/L

2

Total Suspended Solids

6

mg/L

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 7/08/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

 3

mg/L

2

Nitrogen (total)

2.52

mg/L

2

Oil and Grease

2.5

mg/L

2

Phosphorus

4.78 

mg/L

2

Total Suspended Solids

5

mg/L

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 3/07/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

 5

mg/L

2

Nitrogen (total)

 2.93

mg/L

2

Oil and Grease

 1.5

mg/L

2

Phosphorus

 4.71

mg/L

2

Total Suspended Solids

 6

mg/L

Right click on the table above to export as a spreadsheet. 

Date Sample Taken: 5/06/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

 1

mg/L

2

Nitrogen (total)

 3.5

mg/L

2

Oil and Grease

 1.5

mg/L

2

Phosphorus

 5.35

mg/L

2

Total Suspended Solids

 3

mg/L

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 1/05/2012

 

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

 5

mg/L

2

Nitrogen (total)

 2.37

mg/L

2

Oil and Grease

 1.5

mg/L

2

Phosphorus

 6.22

mg/L

2

Total Suspended Solids

 6

mg/L

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 3/04/2012

Licence Number: 3850 

Sampling Point

Pollutant

Result   

Unit

2

Biochemical Oxygen Demand

 6

mg/L

2

Nitrogen (total)

 2.66

mg/L

2

Oil and Grease

 1.5

mg/L

2

Phosphorus

 6.1

mg/L

2

Total Suspended Solids

 17

mg/L

Right click on the table above to export as a spreadsheet.

Pollution Incident Response Management Plan (PIRMP)

Council has developed a Pollution Incident Response Management Plan (PIRMP) that will guide Council's response in the event of any pollution incidents that may occur at the Dubbo Sewage Treatment Plant. The PIRMP for the Dubbo Sewage Treatment Plant can be viewed below.

Pollution Incident Response Management Plan - Dubbo Sewage Treatment Plant Pollution Incident Response Management Plan - Dubbo Sewage Treatment Plant (423 KB)

 

John Gilbert Water Treatment Plant

The John Gilbert Water Treatment Plant is also licenced by the NSW Environment Protection Authority, and backwash water discharged to the Macquarie River must be monitored in accordance with the terms of the licence. The licence number is 11694.

John Gilbert Water Treatment Plant Environment Protection Licence John Gilbert Water Treatment Plant Environment Protection Licence (117 KB)

For more information about licences, click here: http://www.environment.nsw.gov.au/epa/

 

The following table contains monthly monitoring data showing the acceptable ranges of pollutants in the backwash water as determined by the EPA, and the actual measurement of the pollutants present. 

 

Date Sample Taken: 23/04/2013

Date Obtained: 03/05/2013

Date Published: 06/05/2013

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

7

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

9

1

 

pH

6.5-8.5

mg/L

8

Right click on the table above to export as a spreadsheet  

Date Sample Taken: 27/03/2013

Date Obtained: 04/04/2013

Date Published: 08/04/2013

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

2.5

1

 

Total Suspended Solids

0-15

mg/L

22

1

 

pH

6.5-8.5

mg/L

8.5

Right click on the table above to export as a spreadsheet  

Date Sample Taken: 28/02/2013

Date Obtained: 07/03/2013

Date Published: 11/03/2013

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

2

1

 

Oil and Grease

0-2

mg/L

2.5

1

 

Total Suspended Solids

0-15

mg/L

14

1

 

pH

6.5-8.5

mg/L

8.8

Right click on the table above to export as a spreadsheet 

Date Sample Taken: 30/01/2013

Date Obtained: 08/02/2013

Date Published: 11/03/2013

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

44

1

 

pH

6.5-8.5

mg/L

8.5

Right click on the table above to export as a spreadsheet 

Date Sample Taken: 19/12/2012

Date Obtained: 27/12/2012

Date Published: 02/01/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

4

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

6

1

 

pH

6.5-8.5

mg/L

8.7

Right click on the table above to export as a spreadsheet

Date Sample Taken: 27/11/2012

Date Obtained: 7/12/2012

Date Published: 17/12/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

11

1

 

pH

6.5-8.5

mg/L

8.6

Right click on the table above to export as a spreadsheet

Date Sample Taken: 17/10/2012

Date Obtained: 24/10/2012

Date Published: 6/11/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

8

1

 

pH

6.5-8.5

mg/L

8.7

Right click on the table above to export as a spreadsheet

Date Sample Taken:12/09/2012

Date Obtained: 21/09/2012

Date Published: 16/10/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

12

1

 

pH

6.5-8.5

mg/L

9.1

Right click on the table above to export as a spreadsheet

Date Sample Taken: 08/08/2012 

Date Obtained: 28/08/2012

Date Published: 17/09/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

2.5

1

 

Total Suspended Solids

0-15

mg/L

6

1

 

pH

6.5-8.5

mg/L

8.7

Right click on the table above to export as a spreadsheet

Date Sample Taken: 31/07/2012 

Date Obtained: 08/08/2012

Date Published: 10/08/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

2.5

1

 

Total Suspended Solids

0-15

mg/L

10

1

 

pH

6.5-8.5

mg/L

8.8

Right click on the table above to export as a spreadsheet. 

Date Sample Taken: 19/06/2012 

Date Obtained: 27/06/2012

Date Published: 26/07/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

9

1

 

pH

6.5-8.5

mg/L

8.4

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 8/05/2012 

Date Obtained: 14/05/2012

Date Published: 29/06/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

9

1

 

pH

6.5-8.5

mg/L

8.6

Right click on the table above to export as a spreadsheet.

Date Sample Taken: 3/04/2012 

Date Obtained: 13/04/2012

Date Published: 29/06/2012

Licence Number: 11694  

Sampling Point 

Monitoring frequency required by licence 

Pollutant

Acceptable Range 

 Unit

Result

1

Monthly during discharge

Biochemical Oxygen Demand

0-10

mg/L

1

1

 

Oil and Grease

0-2

mg/L

1.5

1

 

Total Suspended Solids

0-15

mg/L

14

1

 

pH

6.5-8.5

mg/L

8.6

Right click on the table above to export as a spreadsheet.

 

The unit “cfu/100 mL” refers to the number of colony forming units in a 100 millilitre sample. It is a biological measure of viable bacterial cells in the water.

Electrical conductivity is measured in units of micro Siemens per centimetre (µS/cm). It is an indication of the amount of nutrient, impurities or salts in solution.

 

Pollution Incident Response Management Plan (PIRMP)

Council has developed a Pollution Incident Response Management Plan (PIRMP) that will guide Council's response in the event of any pollution incidents that may occur at the John Gilbert Water Treatment Plant. The PIRMP for the John Gilbert Water Treatment Plant can be viewed below.

Pollution Incident Response Management Plan - Dubbo Water Treatment Plant Pollution Incident Response Management Plan - Dubbo Water Treatment Plant (413 KB)

 

Whylandra Waste Depot Sampling Results

An extensive ongoing environmental monitoring regime has been conducted at the Whylandra Waste Disposal Depot (WWDD) since January 1998. The WWDD is operated in accordance with the licence number 6058 issued by the NSW Environmental Protection Authority (EPA) under Protection of the Environmental Operations Act 1997 (POEO Act). The EPA licence describes the monitoring requirements (ie monitoring point locations, sampling methods, frequency of measure and sampling parameters) of surface water, groundwater, leachate and landfill gas. Under recent changes to the POEO Act, licencees are required to publish environmental monitoring data that has been collected as a result of a licence condition, in accordance with section 66(6) of the POEO Act.

 

Whylandra Waste Depot Sampling Results - October 2012 Whylandra Waste Depot Sampling Results - October 2012 (27 KB)